7SV600 |
Numerical Circuit-Breaker Failure Protection |
|
The 7SV600 is a numerical relay used for circuit breaker failure protection.
This condition is when the circuit breaker fails to correctly open and
clear the fault after single- or three-pole trip commands have been issued
by the protection. It is then necessary to trip the relevant bus-bar zone
(section) to ensure fault clearance. Generally, the monitoring of the
current suffices as the criteria for the indication that the circuit breaker
has successfully cleared the fault ("current condition"). However,
under certain fault conditions, (e.g. overvoltage) little or no current
may flow making the measurement of current unreliable for indication of
the circuit breaker status ("no current condition"). The 7SV600
will operate correctly for both these conditions. The high security of
the relay (against overfunction) is achieved with a fast current reset
time and a 2-out-of-4 current measurement checks. The relay is suitable
for use at all voltage levels and in all applications. The current transformers
can either be of the closed iron core or linear type. The relay can be
incorporated in conventional switchgear systems and modern substation
control systems e.g. Siemens SICAM.
|
|
7SV512 |
Numerical Circuit-Breaker Failure Protection |
|
The 7SV512 is a numerical relay used for circuit breaker failure protection.
This condition is when the circuit breaker fails to correctly open and
clear the fault after single- or three-pole trip commands have been issued
by the protection. It is then necessary to trip the relevant bus-bar zone
(section) to ensure fault clearance. Generally, the monitoring of the
current suffices as the criteria for the indication that the circuit breaker
has successfully cleared the fault ("current condition"). However,
under certain fault conditions, (e.g. overvoltage) little or no current
may flow making the measurement of current unreliable for indication of
the circuit breaker status ("no current condition"). The 7SV512
will operate correctly for both these conditions. The high security of
the relay (against overfunction) is achieved with a unique microprocessor
independent pole discrepancy protection is included. The relay is suitable
for use at all voltage levels and in all applications. The current transformers
can either be of the closed iron core or linear type. The relay can be
incorporated in conventional switchgear systems and modern substation
control systems e.g. Siemens SINAUT LSA.
|
|
7VK512 |
Numerical Auto-Reclosure / Synchro-check relay |
|
The 7VK512 is a highly flexible single and/or three
pole auto-reclose relay, with or without a check-synchronism function. The
7VK512 can also be used as a check-synchronism relay only. This relay is
used for the automatic reclosure of a circuit breaker, after this circuit
breaker has tripped due to a fault. The check-synchronism function ensures
that the two circuits being connected by closing the circuit breaker, meet
the desired requirements before the close command is issued. The system
interface is available as a fibre optic interface for connection to either
the substation control system SINAUT LSA or to a central data protection
unit.
Functions
|
|
7XV75 |
Test Switch |
|
The test switch serves in the testing of protection devices using the secondary injection test sets 7VP15 (Omicron CMC 56) or 7VP48/49. |
|
7VP151 |
Portable Test System |
|
The current range extends from 0 to 12.5 A, the voltage range from 0 to 125 V. For higher currents, voltages or power requirements, the supplementary six-phase current amplifier unit 7VP153 and the three-phase voltage and current amplifier 7VP155 are offered. For single-phase applications, the single phase test unit 7VP152 is offered. |
|
7SN60 |
Transient Earth Fault Relay |
|
The highly sensitive transient earth-fault relay 7SN60 determines the direction of transient and continuous earth faults in systems with isolated neutral, in systems with high-impedance resistive earthing and in compensated systems. |