SIPROTEC 7SJ86
The SIPROTEC 7SJ86 overcurrent protection is specifically designed to act as backup or emergency protection for the line protection devices.
Its modular structure and flexibility, coupled with the high-performing DIGSI 5 engineering tool, allows the SIPROTEC 5 7SJ86 to offer future-oriented solutions for protection, control, automation, monitoring, and Power Quality (PQ) basic.
Basic Features
- Overcurrent protection as backup / emergency line protection for all voltage levels with 3-pole tripping
- Optimized tripping times due to directional comparison and protection data communication
- Uses pulse detection method to detect transient ground faults
- Fault Locator Plus function with inhomogeneous line sections and targeted automatic overhead-line section reclosing (AREC) to accurately identify fault location
- Arc protection
- Automatic frequency relief for underfrequency load shedding, taking the changed infeed conditions arising from decentralized power generation into consideration
- Protection from overvoltage and undervoltage
- Frequency and frequency change protection for load shedding applications
- Configurable power protection (active or reactive)
- Directional reactive power undervoltage protection (QU protection)
- Circuit-Breaker failure protection and reignition monitoring
- Reliable data transmission via PRP and HSR redundancy protocols
- Extensive cybersecurity functionality (e.g. role-based access control (RBAC), protocolling security-related events, signed firmware or authenticated network access IEEE 802.1X)
- Provides simple, quick and secure access to the device data via a standard Web browser to display all information, diagnostic data, vector diagrams, single-line diagrams, and device display pages
- Phasor Measurement Unit (PMU) for synchrophasor measured values and IEEE C37.118 protocol
- Time synchronization using IEEE 1588
- Enables powerful fault recording (buffer for a max. record time of 80 sec. at 8 kHz or 320 sec. at 2 kHz)
- Allows flexible adjustment of I/O quantity structure within the scope of the SIPROTEC 5 modular system