SIPROTEC 7UT82

The SIPROTEC 7UT82 transformer differential protection is specifically designed to protect two-winding transformers.

It acts as the main protection for transformers and contains many other protection and monitoring functions. The additional protection functions can also provide backup protection for objects (e.g. cables, lines, shunt reactor) that need to be protected subsequently. The modular expandability of the hardware supports this process.

Its modular structure and flexibility, coupled with the high-performing DIGSI 5 engineering tool, allows the SIPROTEC 5 7UT82 to offer future-oriented solutions for protection, control, automation, monitoring, and Power Quality (PQ) basic.

Basic Features

  • 1 differential protection function (standard or auto transformer) with additional stabilization; up to 2 restricted ground-fault protection functions
  • Transformer differential protection for two-winding transformers with versatile, additional protection functions
  • Transformer differential protection for phase-angle regulating transformers of the single core type
  • Universal usability of the permissible measuring points
  • Applicable from average to extra-high voltage
  • Protects standard power transformers, auto transformers, short lines, cables, longitudinal and shunt reactors, and motors
  • Increased sensitivity with near-neutral-point ground faults through a separate restricted ground-fault protection
  • Able to flexibly adapt to the transformer vector group
  • Controls closing and overexcitation processes
  • Safe behavior in case of current-transformer saturation with different degrees of saturation
  • Adaptive adaptation of the operate curve to the transformer tap position
  • Arc protection
  • Up to 2 optional pluggable communication modules, usable for different and redundant protocols (IEC 61850-8-1,IEC 60870-5-103, IEC 60870-5-104, Modbus TCP, DNP3 serial and TCP, PROFINET I/O)
  • Reliable data transmission via PRP and HSR redundancy protocols
  • Extensive cybersecurity functionality (e.g. role-based access control (RBAC), protocolling security-related events, signed firmware or authenticated network access IEEE 802.1X)
  • Provides simple, quick and secure access to the device via a standard Web browser to display all information and diagnostic data, as well as vector diagrams, single-line diagrams, and device display pages
  • Time synchronization using IEEE 1588
  • Enables powerful fault recording (buffer for a max. record time of 80 sec. at 8 kHz or 320 sec. at 2 kHz)