SIPROTEC 7UT86

The SIPROTEC 7UT86 transformer differential relay is specifically designed to protect three-winding transformers (3 sides) and it supports all SIPROTEC 5 system characteristics.

It acts as the main protection for transformers and contains many other protection and monitoring functions. The additional protection functions can also provide backup protection for objects (e.g. cables, lines, shunt reactor) that need to be protected subsequently. The modular expandability of the hardware supports this process. 

Its modular structure and flexibility, coupled with the high-performing DIGSI 5 engineering tool, allows the SIPROTEC 5 7UT86 to offer future-oriented solutions for protection, control, automation, monitoring, and Power Quality (PQ) basic.

Basic Features

  • 1 differential protection function (standard) with additional stabilization; up to 3 restricted ground-fault protection functions
  • For auto transformer applications, two differential protection functions can be processed in an auto transformer function group
  • Transformer differential protection for three-winding transformers with versatile, additional protection functions (expandable to four-winding transformers)
  • Transformer differential protection for phase-angle regulating transformers of the single core type and special transformers
  • Universal usability of the permissible measuring points
  • Applicable from average to extra-high voltage
  • Protects standard power transformers, auto transformers, short lines, cables, longitudinal and shunt reactors, and motors
  • Adaptive adaptation of the operate curve to the transformer tap position
  • Increased sensitivity with near-neutral-point ground faults through a separate restricted ground-fault protection
  • Point-on-wave switching
  • Additional current and voltage inputs can be supplements for standard protection functions (e.g. overcurrent, voltage frequency)
  • Dynamic Voltage Control (DVC) to adapt the voltage target value via a power direction dependent characteristic curve with strong infeed of regenerative energies
  • Fault Locator Plus function with inhomogeneous line sections and targeted automatic overhead-line section reclosing (AREC) to accurately identify fault location
  • Arc protection
  • Voltage controller function ANSI 90V for two-winding transformers, three-winding transformers and grid coupling transformers with parallel control (master/follower, circulating reactive current minimization)
  • Up to 4 pluggable communication modules, usable for different and redundant protocols (IEC 61850-8-1, IEC 61850-9-2 Client, IEC 60870-5-103, IEC 60870-5-104, Modbus TCP, DNP3 serial and TCP, PROFINET I/O, and PROFINET I/O S2 redundancy)
  • Reliable data transmission via PRP and HSR redundancy protocols
  • Extensive cybersecurity functionality (e.g. role-based access control (RBAC), protocolling security-related events, signed firmware or authenticated network access IEEE 802.1X)
  • Provides simple, quick and secure access to the device via a standard Web browser to display all information and diagnostic data, as well as vector diagrams, single-line diagrams, and device display pages
  • Captures operational measured variables and protection function measured values for the evaluation of the systems to support commissioning and analyze faults
  • Frequency tracked protection functions over a wide frequency range (10 Hz to 90 Hz) and the option to assign the protection functions in a single device to different frequency tracking groups.
  • Phasor Measurement Unit (PMU) for synchrophasor measured values and IEEE C37.118 protocol
  • Enables powerful fault recording (buffer for a max. record time of 80 sec. at 8 kHz or 320 sec. at 2 kHz)
  • Flexible adjustment of I/O quantity structure within the scope of the SIPROTEC 5 modular system